Here's one that matters more than its name lets on — Tools, Materials & Wiring Methods. If you remember one thing, make it this: Every material an electrician installs — conductor, cable or raceway, box, device, and overcurrent device — is selected by the code for the load and the location, and the tools of the trade exist to install it cleanly without damaging the insulation that keeps it safe. Do this right and the inspection is a walk-through instead of a punch list.
Conductors
Copper is the standard for branch circuits; aluminum is common for larger feeders and services because it's lighter and cheaper, but it needs terminations listed for it. Conductors are sized by AWG (American Wire Gauge — smaller number, bigger wire) up to 4/0, then by kcmil. Insulation matters: THHN/THWN-2 is the general-purpose building wire pulled in conduit; its 90°C rating helps when derating, but the 75°C terminal rating of most equipment caps the ampacity you can actually use. White or gray marks the grounded (neutral) conductor and green or bare the equipment grounding conductor; other colors are ungrounded ("hot").
Cables and raceways
- NM cable (Type NM-B, "Romex") — the residential workhorse: hots, neutral, and bare ground in a plastic jacket. Permitted in dwellings and some other buildings by construction type; not outdoors, not where subject to damage, and not in many commercial occupancies.
- MC cable — conductors in an interlocked metal armor; the commercial favorite above ceilings and in walls.
- UF cable for direct burial; SE/SER for dwelling services and feeders.
- EMT — thin-wall steel conduit, bent by hand and joined with set-screw or compression fittings; the standard exposed commercial raceway.
- Rigid metal conduit and IMC — threaded and heavy, for services, outdoors, and where damage is likely. PVC conduit underground and in corrosive locations. Flexible metal and liquidtight conduit for final connections to equipment. Each has its own article in NEC Chapter 3 with rules on where it may be used, how it's supported, and how many conductors fit.
Boxes, devices, and distribution equipment
Boxes house every splice and device; metal or nonmetallic, sized by box fill (Article 314), and kept accessible. Devices: 15- and 20-amp receptacles (tamper-resistant where required in dwellings, weather-resistant outdoors), switches, dimmers, occupancy sensors. Luminaires and their drivers. Panelboards and load centers with the main breaker, bus, branch breakers, and neutral and ground bars. Disconnects, transformers, motor starters, and drives on commercial and industrial work. GFCI and AFCI protection in breakers or devices where the code requires it.
Tools and test instruments
In the pouch: lineman's pliers, diagonal cutters, needle-nose pliers, wire strippers, screwdrivers (including square-drive), nut drivers, a utility knife, a torpedo level, and a tape. On the truck: a fish tape for getting conductors through raceways, a hand bender for small EMT, a hammer drill, an impact driver, hole saws, a knockout punch set, a bandsaw, and a torque screwdriver and wrench — the NEC requires terminations tightened to the manufacturer's torque. For testing: a non-contact voltage tester for a first warning, a multimeter or two-pole tester rated for the system to verify absence of voltage, a clamp meter, a receptacle tester, and on commercial work a megohmmeter for insulation resistance.
Going Deeper (Intermediate)
The craft in conduit work is bending: offsets, saddles, kicks, and 90s laid out so the run follows the building, parallel and level. Conduit fill (Chapter 9, Table 1) limits how many conductors go in a raceway, and the adjustment factors in Article 310 reduce ampacity when more than three current-carrying conductors share a raceway or the ambient is hot.
Terminations fail more often than conductors do. Strip to the right length, land the conductor under the right terminal, use a connector listed for the wire type (copper and aluminum are not interchangeable without a lug listed for both), and torque it. A loose connection heats, arcs, and eventually fails — a common cause of electrical fires in finished buildings.
Advanced / Pro-Level
Pros standardize materials by spec: the Division 26 specifications and the engineer's drawings call out raceway types, conductor insulation, device grades, and manufacturer requirements, and the submittals prove the material matches before it arrives. They understand listing and labeling — equipment must be listed by a nationally recognized testing laboratory and installed per its listing, and a field modification can void it. They know how short-circuit current ratings must meet the available fault current at the point of installation, and they treat test instruments as safety equipment: CAT III or CAT IV rated, leads inspected, and a live-dead-live check before trusting a reading.
Practice Challenge
A homeowner asks a contractor to run power to a new detached workshop. The electrician proposes NM cable stapled along the fence to the building. What's wrong? (Answer: NM cable isn't permitted exposed outdoors or where subject to damage; the feeder needs a wiring method rated for wet locations and burial — UF cable or conductors in PVC or rigid conduit at the required depth — plus a disconnecting means and a grounding electrode system at the workshop as a separate structure.)
In Practice
An electrician who pulls THHN through clean, deburred EMT with lubricant and torques every lug passes the insulation test and never gets a callback. One who drags conductors over a sharp coupling edge and hand-tightens the breakers gets a nuisance trip in year three and a burned bus in year ten.
Common Mistakes to Avoid
- Using NM cable where the code doesn't allow it
- Overfilling boxes and raceways
- Mixing copper and aluminum conductors on a lug not listed for both
- Hand-tightening terminations instead of torquing them
Takeaway: Every material an electrician installs — conductor, cable or raceway, box, device, and overcurrent device — is selected by the code for the load and the location, and the tools of the trade exist to install it cleanly without damaging the insulation that keeps it safe.